Pow-Sys Güç Sistemleri logoPow-Sys Güç Sistemleri
Request a QuoteTürkçe
Industrial energy and power systems field application

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair

Transformer maintenance in Bursa: routine tests, oil analysis, DGA, fault repair, commissioning and planned maintenance service.

Engineering-FocusedField ExperienceStandards ComplianceEnergy EfficiencyFast Proposal24/7 SupportCertified TeamMeasurement & ReportingData-Driven Improvement
MV switchgear, power transformer connection checks and electrical transformer tests during transformer maintenance in Bursa
Transformer maintenance, testing and fault repair integrated with MV switchgear for power and distribution transformers in Bursa.

Summary Highlights

  • Transformer maintenance, periodic maintenance, routine tests, measurements, maintenance forms and detailed condition assessment reports for power and distribution transformers in Bursa
  • Field transformer tests such as TTR (turns ratio) test, winding DC resistance, insulation (megger) test, short-circuit impedance, load and no-load losses, power factor / tan-delta, magnetic balance and vector group checks
  • Transformer oil testing and oil analysis according to IEC/ASTM standards, including DGA, dielectric strength, moisture, acidity, color and furanic compounds, with a technical roadmap for oil treatment, oil regeneration and mobile oil processing solutions
  • Transformer acceptance tests, testing and commissioning procedures (FAT/SAT), current / voltage transformer tests, protection relay secondary / primary tests and MV switchgear function checks after factory tests for new or renewed transformers
  • Transformer fault maintenance and repair, transformer repair in Bursa, on-site mobile repair service, hermetic distribution transformer and dry-type transformer repair-maintenance, bushing and gasket replacement, oil leak elimination, cooling system and OLTC maintenance
  • Integrated solutions for MV transformer maintenance-repair, transformer service and HV/MV tests, including transformer measurements, grounding and touch voltage tests, thermal camera infrared checks and Bursa HV/MV testing, maintenance and repair services
  • As a Bursa transformer maintenance company and service provider, we offer contracted transformer maintenance, periodic maintenance and project-based maintenance-repair solutions in Bursa center, Nilufer OSB, DOSAB, Hasanaga, Kayapa, Kestel, Gursu, Inegol OSB and similar regions

Service Details

What is transformer maintenance and testing service in Bursa

We provide transformer maintenance, transformer tests, transformer oil analysis, fault maintenance-repair and transformer testing-commissioning services for industrial facilities, factories in organized industrial zones, power generation-distribution facilities and large buildings using power and distribution transformers in Bursa. As a Bursa transformer maintenance company and transformer service provider, our aim is to ensure safe and efficient transformer operation, reduce unplanned outages and detect faults before they occur through a predictive maintenance approach. For related context, see Bursa Transformer Periodic Inspection and Testing.

How it differs from transformer operation responsibility

While transformer operation responsibility service covers regulation-compliant operation, record follow-up and signing responsibility, the Bursa transformer maintenance, testing and repair services described on this page cover periodic maintenance, electrical tests, transformer oil testing and analysis, transformer measurements, fault maintenance and MV transformer maintenance-repair works directly related to the transformer itself. The two services complement each other but their scopes and responsibility areas are different. For related context, see Bursa Generator Periodic Inspection.

Why transformer maintenance is necessary

Transformer maintenance is required to keep the ageing insulation system, loosening connection points and transformer oil losing its properties under control against heating-cooling cycles, short circuits, impulse voltages, mechanical stresses and environmental effects. If regular maintenance and routine tests are not performed, serious risks such as internal faults, dielectric breakdown of oil, busbar and terminal burns, circuit breaker trips and even fire may occur. Therefore, electrical transformer maintenance is an inseparable part of periodic inspection obligations under Law No. 6331 and the Regulation on Health and Safety Conditions in the Use of Work Equipment. For related context, see Bursa Grounding Measurement and Report.

Site survey and existing condition assessment

We begin with a site survey and existing condition assessment. Transformer type (oil-immersed or dry-type), rating, voltage level, brand, age, connected MV switchgear arrangement, protection-measurement relays, cable supplies and previous transformer maintenance and test reports are reviewed. When required, factory routine tests and previous acceptance tests are also reviewed, the scope of electrical tests to be applied in the field is clarified and a maintenance program suitable for outage windows is prepared. For related context, see Bursa High Voltage (HV) and Medium Voltage (MV) Services.

Electrical transformer tests

Our routine transformer test package includes the main electrical tests answering the question of which transformer tests are performed: TTR (turns ratio) test, winding DC resistance measurement, insulation (megger) test, and where required, power factor / tan-delta, short-circuit impedance, load and no-load loss measurements, magnetic balance and vector group checks. With these tests, winding faults, contact problems, connection errors, insulation weaknesses, unbalanced loading and installation-related errors are detected at an early stage.

Dry-type and oil-immersed transformer checks

There are some differences between routine tests applied to dry-type transformers and oil-immersed transformers. In dry-type transformers, partial discharge, surface contamination, temperature rise and air-channel cleanliness come to the fore; in oil-immersed transformers, additional parameters such as oil dielectric strength, moisture in oil and cellulose insulation condition are checked. Within this framework, power transformer tests and distribution transformer tests are planned separately; special steps are defined when dry-type transformer repair-maintenance or hermetic distribution transformer maintenance is required.

Integration with MV switchgear, relay and cable tests

Transformer electrical tests should be considered together with the protection system and cables on the MV side. Therefore, when necessary, MV switchgear tests, circuit breaker and disconnector checks, protection relay secondary / primary tests, cable insulation tests, grounding resistance and touch voltage measurements are planned as a single package for the transformer substation. HV transformer tests and commissioning steps before energization are carried out in an integrated manner with our HV/MV testing, maintenance and repair service.

Transformer oil testing and DGA analysis

In oil-immersed transformers, transformer oil testing and oil analysis are among the most critical predictive maintenance tools that provide information about internal health. Oil samples are taken according to IEC/ASTM standards and parameters such as dissolved gas analysis (DGA), breakdown voltage (BDV), moisture, acidity (TAN), color, sludge tendency and, when required, furanic compounds are examined. Thus, arcing, partial discharge, overheating, cellulose aging and insulation damage that is difficult to reverse can be detected at an early stage even when the transformer appears normal from outside.

Oil treatment, regeneration and mobile oil processing

According to transformer oil test and oil analysis results, actions such as oil treatment, oil regeneration, complete oil replacement, elimination of oil leaks or reassessment of the loading profile are recommended. With mobile oil treatment devices, oil processing can be carried out on site; in this way, the electrical and chemical properties of transformer oil can be improved without removing the transformer from the field. When oil analysis trends are followed over years, the maintenance interval can be optimized with numerical data.

Mechanical and visual checks

During mechanical and visual checks, the transformer tank, expansion tank, radiators, connection bolts, terminals, MV/LV busbars, cable terminations and joints, bushings, tap changer and cooling fans/pumps are examined in detail. Points with abnormal temperature rise observed during infrared scans with a thermal camera may indicate loose connection, overload, unbalanced phase current or internal fault. The practical answer to how a faulty transformer is detected is the combined evaluation of these measurements, tests and observations; when required, tightening, cleaning, oxide removal, improvement of insulation distances and part replacement are performed on site.

Transformer fault repair and on-site service

Transformer fault maintenance-repair works cover many items such as elimination of oil leaks, gasket and bushing replacements, tap changer maintenance and setting, renewal of cooling fans/pumps, revision of circuit breakers and disconnectors in MV switchgear, and cleaning of transformer cabinets and panels. In cases with heavy winding damage or comprehensive oil processing needs, transformer repair, winding renewal, oil treatment / oil regeneration and workshop tests are organized together with partner workshops; field and laboratory results are evaluated together.

Acceptance tests and commissioning

In new transformer substation investments or capacity increase projects, we work together with our LV/MV/HV project design and consultancy team for transformer selection, MV switchgear and cable projects, protection relay coordination, factory tests, field acceptance tests, testing and commissioning steps and energization scenarios. Electrical tests performed during first commissioning create reference values for future periodic maintenance, measurements and tests and allow the aging curve of the equipment to be monitored numerically.

Maintenance planning and production outage management

When planning transformer maintenance, production outages, maintenance windows, shift order, number of transformers and criticality of the facility are evaluated together. Some checks are performed while energized, such as online measurements and thermal scans, while comprehensive electrical tests are performed after the transformer is safely de-energized. Thus, occupational safety rules are followed and transformer maintenance intervals become compatible with production plans of facilities in Bursa. Contracted maintenance, periodic programs and emergency response services can be configured together when needed.

Transformer maintenance and test report

All measurement and test results are delivered as an official transformer maintenance and test report together with the devices used, reference / limit values, photographs and thermal images when required. The report clearly states tests performed, detected nonconformities, recommended corrective-preventive actions and parameters to be followed. These reports and the transformer maintenance / test forms used can serve as technical references in your electrical installation periodic inspection and other examination files.

How the transformer maintenance interval is determined

The transformer maintenance interval is determined according to transformer rating, loading profile, environmental conditions, facility criticality, previous faults and test results. The general approach is to perform comprehensive transformer maintenance and routine tests at least once a year for power and distribution transformers, and to monitor the condition with intermediate oil analyses and control measurements when required. If desired, this continuity can be managed by integrating it with transformer operation responsibility and HV operation responsibility contracts.

How Bursa transformer maintenance prices are determined

The service fee is determined project-specifically according to the number and rating of transformers, whether they are oil-immersed or dry-type, requested test scope such as routine tests, acceptance tests, oil tests, MV switchgear and cable tests, time to be spent on site, special test equipment to be used and facility location. In Bursa and nearby regions, especially Nilufer OSB, DOSAB, Hasanaga, Kayapa, Kestel, Gursu and Inegol OSB, we perform site surveys and provide clear, understandable and comparable proposal options for transformer maintenance-repair, transformer repair in Bursa and testing-commissioning.

Transformer oil sampling, oil testing, oil analysis and grounding measurement in Bursa
Transformer maintenance and testing study where oil testing and DGA are reported together with grounding measurements.

Frequently Asked Questions

How often should transformer maintenance be performed? Is it mandatory?

For power and distribution transformers, the general approach is to perform comprehensive maintenance and routine tests at least once a year. In transformers with high loading, dusty-humid environments or critical processes, intermediate checks and oil testing / analysis can be repeated more frequently. Transformer maintenance is within periodic inspection obligations under Law No. 6331 and the Regulation on Health and Safety Conditions in the Use of Work Equipment.

Who can perform transformer maintenance?

Transformer maintenance should be performed by electrical / electrical-electronics engineers experienced in high voltage and trained technical teams who know the relevant standards and regulations and can work with suitable test devices. For MV transformers, working under the supervision of EMO-registered authorized engineers is important for both safety and official reporting.

Which transformer tests are performed?

The main electrical transformer tests we apply in the field are TTR (turns ratio), winding DC resistance, insulation (megger), power factor / tan-delta when required, short-circuit impedance, load and no-load loss measurements, vector group and magnetic balance checks, and partial discharge monitoring. Depending on the project, MV switchgear tests, protection relay tests, cable insulation tests, grounding resistance-touch voltage measurements and commissioning steps can also be included.

Why are transformer oil testing and DGA so important?

Transformer oil is a critical component that provides both insulation and cooling. Oil tests and DGA performed according to IEC/ASTM standards examine dielectric strength, moisture, acidity and gases formed in oil, revealing internal faults such as arcing, partial discharge, overheating and cellulose aging at an early stage. It should be repeated periodically especially in aged transformers, facilities with changing loading profiles or previous oil results approaching limits.

How can a faulty transformer be detected?

Fault indications include abnormal noise, smell or vibration, sudden changes in oil level, oil leakage, bushing cracks, abnormal temperature rise seen on thermal camera, frequent trips of protection relays and decreases in insulation / BDV values. When such signs are observed, the transformer should not be forced to remain energized; a specialist service capable of tests, oil analysis and visual checks should be called.

Can we receive on-site transformer repair service in Bursa?

Yes. We provide on-site fault maintenance-repair and mobile transformer repair service for organized industrial zones and industrial facilities in Bursa. Oil leaks, gasket and bushing problems, loose connections, hot spots, cooling system faults and protection relay setting problems can often be resolved on site with mobile equipment. For more comprehensive damage, workshop repair, oil treatment and additional testing are organized with partner workshops.

What is a transformer maintenance contract?

A transformer maintenance contract is a written agreement in which annual or multi-year maintenance, routine tests, oil tests and required MV switchgear-cable checks are planned in advance for the power and distribution transformers in your facility. Contracted maintenance prevents forgotten inspection dates, meets legal requirements regularly, reduces fault risks and makes budget planning more predictable.

Which acceptance tests and commissioning procedures are applied for a new transformer?

Before energizing a new or renewed transformer, visual and mechanical checks, insulation tests, TTR, winding resistance measurements, load / no-load loss tests, short-circuit impedance measurement, partial discharge checks and, where required, high-voltage withstand tests are performed. In parallel, MV switchgear tests, protection relay tests, grounding and touch voltage measurements are completed. These steps form the field acceptance and commissioning procedure.

Let us bring your project to life together.

Contact us now for a site survey and preliminary discussion.

Contact Us