Pow-Sys Güç Sistemleri logoPow-Sys Güç Sistemleri
Request a QuoteTürkçe
LV, MV and HV electrical services and power systems field application

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair

Transformer maintenance in Bursa: routine tests, oil analysis, DGA, fault repair, commissioning and planned maintenance service.

Engineering-FocusedField ExperienceStandards ComplianceEnergy EfficiencyFast Proposal24/7 SupportCertified TeamMeasurement & ReportingData-Driven Improvement
MV switchgear, power transformer connection checks and electrical transformer tests during transformer maintenance in Bursa
Transformer maintenance, testing and fault repair integrated with MV switchgear for power and distribution transformers in Bursa.

Last updated: May 2026

What changed: Service scope, report outputs, official sources, pre-proposal information and technical transparency notes were reviewed for the current period.

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair Summary

  • Transformer maintenance, periodic maintenance, routine tests, measurements, maintenance forms and detailed condition assessment reports for power and distribution transformers in Bursa
  • Field transformer tests such as TTR (turns ratio) test, winding DC resistance, insulation (megger) test, short-circuit impedance, load and no-load losses, power factor / tan-delta, magnetic balance and vector group checks
  • Transformer oil testing and oil analysis according to IEC/ASTM standards, including DGA, dielectric strength, moisture, acidity, color and furanic compounds, with a technical roadmap for oil treatment, oil regeneration and mobile oil processing solutions
  • Transformer acceptance tests, testing and commissioning procedures (FAT/SAT), current / voltage transformer tests, protection relay secondary / primary tests and MV switchgear function checks after factory tests for new or renewed transformers
  • Transformer fault maintenance and repair, transformer repair in Bursa, on-site mobile repair service, hermetic distribution transformer and dry-type transformer repair-maintenance, bushing and gasket replacement, oil leak elimination, cooling system and OLTC maintenance
  • Integrated solutions for MV transformer maintenance-repair, transformer service and HV/MV tests, including transformer measurements, grounding and touch voltage tests, thermal camera infrared checks and Bursa HV/MV testing, maintenance and repair services
  • As a Bursa transformer maintenance company and service provider, we offer contracted transformer maintenance, periodic maintenance and project-based maintenance-repair solutions in Bursa center, Nilufer OSB, DOSAB, Hasanaga, Kayapa, Kestel, Gursu, Inegol OSB and similar regions

Technically reviewed by

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair Scope

What is transformer maintenance and testing service in Bursa

We provide transformer maintenance, transformer tests, transformer oil analysis, fault maintenance-repair and transformer testing-commissioning services for industrial facilities, factories in organized industrial zones, power generation-distribution facilities and large buildings using power and distribution transformers in Bursa. As a Bursa transformer maintenance company and transformer service provider, our aim is to ensure safe and efficient transformer operation, reduce unplanned outages and detect faults before they occur through a predictive maintenance approach. For related context, see Bursa Battery Periodic Inspection.

How it differs from transformer operation responsibility

While transformer operation responsibility service covers regulation-compliant operation, record follow-up and signing responsibility, the Bursa transformer maintenance, testing and repair services described on this page cover periodic maintenance, electrical tests, transformer oil testing and analysis, transformer measurements, fault maintenance and MV transformer maintenance-repair works directly related to the transformer itself. The two services complement each other but their scopes and responsibility areas are different. For related context, see Bursa Lightning Protection Periodic Inspection.

Why transformer maintenance is necessary

Transformer maintenance is required to keep the ageing insulation system, loosening connection points and transformer oil losing its properties under control against heating-cooling cycles, short circuits, impulse voltages, mechanical stresses and environmental effects. If regular maintenance and routine tests are not performed, serious risks such as internal faults, dielectric breakdown of oil, busbar and terminal burns, circuit breaker trips and even fire may occur. Therefore, electrical transformer maintenance is an inseparable part of periodic inspection obligations under Law No. 6331 and the Regulation on Health and Safety Conditions in the Use of Work Equipment. For related context, see Bursa Periodic Inspection and Examination Service.

Site survey and existing condition assessment

We begin with a site survey and existing condition assessment. Transformer type (oil-immersed or dry-type), rating, voltage level, brand, age, connected MV switchgear arrangement, protection-measurement relays, cable supplies and previous transformer maintenance and test reports are reviewed. When required, factory routine tests and previous acceptance tests are also reviewed, the scope of electrical tests to be applied in the field is clarified and a maintenance program suitable for outage windows is prepared. For related context, see Bursa Electrical Installation Periodic Inspection.

Electrical transformer tests

Our routine transformer test package includes the main electrical tests answering the question of which transformer tests are performed: TTR (turns ratio) test, winding DC resistance measurement, insulation (megger) test, and where required, power factor / tan-delta, short-circuit impedance, load and no-load loss measurements, magnetic balance and vector group checks. With these tests, winding faults, contact problems, connection errors, insulation weaknesses, unbalanced loading and installation-related errors are detected at an early stage.

Dry-type and oil-immersed transformer checks

There are some differences between routine tests applied to dry-type transformers and oil-immersed transformers. In dry-type transformers, partial discharge, surface contamination, temperature rise and air-channel cleanliness come to the fore; in oil-immersed transformers, additional parameters such as oil dielectric strength, moisture in oil and cellulose insulation condition are checked. Within this framework, power transformer tests and distribution transformer tests are planned separately; special steps are defined when dry-type transformer repair-maintenance or hermetic distribution transformer maintenance is required.

Integration with MV switchgear, relay and cable tests

Transformer electrical tests should be considered together with the protection system and cables on the MV side. Therefore, when necessary, MV switchgear tests, circuit breaker and disconnector checks, protection relay secondary / primary tests, cable insulation tests, grounding resistance and touch voltage measurements are planned as a single package for the transformer substation. HV transformer tests and commissioning steps before energization are carried out in an integrated manner with our HV/MV testing, maintenance and repair service.

Transformer oil testing and DGA analysis

In oil-immersed transformers, transformer oil testing and oil analysis are among the most critical predictive maintenance tools that provide information about internal health. Oil samples are taken according to IEC/ASTM standards and parameters such as dissolved gas analysis (DGA), breakdown voltage (BDV), moisture, acidity (TAN), color, sludge tendency and, when required, furanic compounds are examined. Thus, arcing, partial discharge, overheating, cellulose aging and insulation damage that is difficult to reverse can be detected at an early stage even when the transformer appears normal from outside.

Oil treatment, regeneration and mobile oil processing

According to transformer oil test and oil analysis results, actions such as oil treatment, oil regeneration, complete oil replacement, elimination of oil leaks or reassessment of the loading profile are recommended. With mobile oil treatment devices, oil processing can be carried out on site; in this way, the electrical and chemical properties of transformer oil can be improved without removing the transformer from the field. When oil analysis trends are followed over years, the maintenance interval can be optimized with numerical data.

Mechanical and visual checks

During mechanical and visual checks, the transformer tank, expansion tank, radiators, connection bolts, terminals, MV/LV busbars, cable terminations and joints, bushings, tap changer and cooling fans/pumps are examined in detail. Points with abnormal temperature rise observed during infrared scans with a thermal camera may indicate loose connection, overload, unbalanced phase current or internal fault. The practical answer to how a faulty transformer is detected is the combined evaluation of these measurements, tests and observations; when required, tightening, cleaning, oxide removal, improvement of insulation distances and part replacement are performed on site.

Transformer fault repair and on-site service

Transformer fault maintenance-repair works cover many items such as elimination of oil leaks, gasket and bushing replacements, tap changer maintenance and setting, renewal of cooling fans/pumps, revision of circuit breakers and disconnectors in MV switchgear, and cleaning of transformer cabinets and panels. In cases with heavy winding damage or comprehensive oil processing needs, transformer repair, winding renewal, oil treatment / oil regeneration and workshop tests are organized together with partner workshops; field and laboratory results are evaluated together.

Acceptance tests and commissioning

In new transformer substation investments or capacity increase projects, we work together with our LV/MV/HV project design and consultancy team for transformer selection, MV switchgear and cable projects, protection relay coordination, factory tests, field acceptance tests, testing and commissioning steps and energization scenarios. Electrical tests performed during first commissioning create reference values for future periodic maintenance, measurements and tests and allow the aging curve of the equipment to be monitored numerically.

Maintenance planning and production outage management

When planning transformer maintenance, production outages, maintenance windows, shift order, number of transformers and criticality of the facility are evaluated together. Some checks are performed while energized, such as online measurements and thermal scans, while comprehensive electrical tests are performed after the transformer is safely de-energized. Thus, occupational safety rules are followed and transformer maintenance intervals become compatible with production plans of facilities in Bursa. Contracted maintenance, periodic programs and emergency response services can be configured together when needed.

Transformer maintenance and test report

All measurement and test results are delivered as an official transformer maintenance and test report together with the devices used, reference / limit values, photographs and thermal images when required. The report clearly states tests performed, detected nonconformities, recommended corrective-preventive actions and parameters to be followed. These reports and the transformer maintenance / test forms used can serve as technical references in your electrical installation periodic inspection and other examination files.

How the transformer maintenance interval is determined

The transformer maintenance interval is determined according to transformer rating, loading profile, environmental conditions, facility criticality, previous faults and test results. The general approach is to perform comprehensive transformer maintenance and routine tests at least once a year for power and distribution transformers, and to monitor the condition with intermediate oil analyses and control measurements when required. If desired, this continuity can be managed by integrating it with transformer operation responsibility and HV operation responsibility contracts.

How Bursa transformer maintenance prices are determined

The service fee is determined project-specifically according to the number and rating of transformers, whether they are oil-immersed or dry-type, requested test scope such as routine tests, acceptance tests, oil tests, MV switchgear and cable tests, time to be spent on site, special test equipment to be used and facility location. In Bursa and nearby regions, especially Nilufer OSB, DOSAB, Hasanaga, Kayapa, Kestel, Gursu and Inegol OSB, we perform site surveys and provide clear, understandable and comparable proposal options for transformer maintenance-repair, transformer repair in Bursa and testing-commissioning.

Reporting, Inspection and Proposal Preparation

Sample Inspection Table

This table summarizes which headings are evaluated on site and which outputs may appear in the report.

Inspected areaChecked criterionReport output
Site and equipment conditionExisting equipment structure, access conditions, visible risks and operating conditionsSite inspection note and prioritized findings list
Document and project conformitySingle-line diagram, current project, labeling, reports and conformity with site implementationDocument conformity assessment and missing record list
Safety and operational riskLife safety, equipment safety, energy continuity and maintenance access risk headingsRisk classification and corrective action recommendations
Measurement, test or inspection needMeasurement, test, visual inspection and technical review items required by the service scopeMeasurement/test plan or inspection scope note
Reporting and follow-upNonconformity priority, follow-up date, responsibility allocation and next stepsPhoto-supported report, action list and follow-up recommendation

Pow-Sys 5-Step Inspection and Follow-Up Workflow

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair is carried out through preliminary review, risk classification, inspection planning, written action list and follow-up/closure logic.

StepOn-site assessmentRecorded output
Preliminary reviewFacility type, voltage level, main equipment, current project/report status and operational expectations are reviewed.Initial technical notes affecting the service scope are created.
Risk classificationLife safety, equipment safety, energy continuity and regulatory compliance are evaluated together.Priority risk headings and field inspection priority are determined.
Inspection and measurement planVisual inspection, testing, measurement, document review and reporting steps required by the service are planned.Site schedule, inspection scope and required record list are clarified.
Written action listDetected deficiencies are separated into actionable corrective items and follow-up dates.Nonconformity, risk level, responsible party and target date are entered into the report.
Follow-up and closurePrevious report items, completed works and continuing risks are compared during the next inspection.Closed/open items and the next inspection note are created.

Pow-Sys Bursa Anonymous Field Data Set

For Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair, facility type, frequent finding, risk type and Pow-Sys action are summarized without sharing real customer or facility names. No quantity or ratio is given where a real numerical record is not maintained.

Reviewed facility typeFrequent findingRisk typePow-Sys action
Industrial zone factoryOutdated single-line diagram or missing field labelIncorrect switching, maintenance confusion and project-site mismatchRevision note, label check and follow-up date are added to the report.
Privately supplied industrial facilityScattered maintenance, test or measurement recordsDelayed maintenance, recurring faults and weak audit readinessRecord organization need and prioritized action list are prepared.
Hospital, shopping mall or critical facilityUnclear critical load, emergency response and continuity planInterruption sensitivity, emergency uncertainty and operational riskCritical load note, separate test need and service scope recommendation are prepared.

Pow-Sys Field Observations and Anonymous Finding Headings

Without sharing real facility or company names, technical findings frequently encountered during field work in Bursa and nearby industrial areas are summarized below. No quantity or ratio is given where a real numerical record is not maintained.

Observation headingTypical site riskPow-Sys action
Outdated project or single-line recordA mismatch between site equipment and documents may increase the risk of wrong decisions, missing maintenance or incorrect switching.Revision need is stated in writing and document follow-up is recommended according to the current field condition.
Labeling and equipment identification gapsUnclear panel, switchgear, cable or equipment names may create confusion for field personnel.Labeling, equipment identification and instruction updates are added to the action list.
Scattered maintenance, test or measurement recordsUntraceable historical records may cause recurring faults, delayed maintenance and audit preparation problems.Report history, follow-up date and records to be completed are written as separate items.
Need for measurement or separate testingGrounding, thermal imaging, relay testing or insulation testing may require separate planning outside the main service.Separately planned test/measurement headings and priority level are added to the report.

Which Service Is Needed? Decision Matrix

During Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair, some findings are reported within the main service scope while some findings may require separate testing, measurement, maintenance or project work.

SymptomLikely needSeparate service needed?Pow-Sys recommendation
Document and site mismatchProject revision, single-line diagram update or labeling workMay be requiredReported in the main service; implementation/revision is planned under a separate scope.
Old measurement or test recordGrounding measurement, thermal imaging, relay test, insulation test or power quality measurementUsually planned separatelyMeasurement/test need, priority level and follow-up date are written in the report.
Equipment fault or maintenance findingTransformer maintenance, panel maintenance, cable/termination check or fault-maintenance-test workMay be a separate serviceMaintenance or implementation need is evaluated separately from the main proposal scope.
Regulatory and reporting gapAuthorized engineer assessment, report follow-up and official-source-based reviewEvaluated within the main serviceCurrent regulation note, report output and responsibility boundary are made visible.

On-Page Tool and Document Previews

Sample tools used during proposal, site visit and reporting are summarized on the page instead of being left only as download links.

ToolOn-page previewPurposeOutput
Pre-survey information formFacility type, location, transformer/main equipment, existing reports and expected visit frequencyClarifying proposal scopeMore accurate survey and proposal plan
Pre-inspection checklistProject, field equipment, safety, maintenance records and measurement/test needAvoiding missed headings during the first site visitList of reviewed criteria
Action tracking tableNonconformity, risk level, responsible party, target date and closure statusKeeping open items traceableTrackable corrective action list
Sample report templateGeneral condition, photo finding, risk level, corrective action and follow-up dateShowing the report format in advanceTechnical report preview
Proposal scope checklistIncluded items, separately planned works, information provided by the employer and emergency support noteMaking contract scope transparentIncluded / separate service distinction

Anonymous Field Case Examples

The following examples show field experience, measurable output and follow-up approach without sharing customer name, facility name, serial number or sensitive operational information.

Anonymous field example - Bursa production facility

Date
May 2026
Facility type
Privately transformer-fed production facility
Anonymous tracking code
bursa-trafo-anonymous-case-2026-01
Previous condition
Existing project documents, field labels and maintenance records were not followed in a single file structure.
Finding
Within Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair, project-site consistency, equipment identification and historical report records included items requiring follow-up.
Action
Nonconformities were separated by risk level; items requiring measurement/testing or maintenance were added to a separate action list.
Measurable output
3 documentation items, 2 equipment identification items and 1 separate measurement/test need were made visible in report format.
Follow-up result
Open items were classified by first follow-up date and next inspection heading.
Limit / note
Customer name, facility name and sensitive technical details are not shared due to privacy and confidentiality.

Anonymous field example - Bursa critical facility

Date
April 2026
Facility type
Hospital, shopping mall or high interruption-sensitivity commercial facility
Anonymous tracking code
bursa-trafo-anonymous-case-2026-02
Previous condition
Critical loads, emergency response expectation and report output scope had not been clarified.
Finding
Power continuity, maintenance access and separate testing need were evaluated together.
Action
Critical headings were written into the report; test/measurement topics to be planned separately were separated from the proposal scope.
Measurable output
2 critical load notes, 1 emergency contact heading and 1 separate test recommendation were written down.
Follow-up result
The site decision was tied to the follow-up plan through authorized engineer assessment and facility management approval.
Limit / note
Final risk level and contract scope are not finalized without an on-site survey.

Anonymous field example - Bursa industrial zone facility

Date
March 2026
Facility type
Privately transformer-fed business in an industrial zone
Anonymous tracking code
bursa-trafo-anonymous-case-2026-03
Previous condition
Maintenance records were kept in different files and previous report open items were not tracked in one list.
Finding
Open follow-up items, completed works and separately planned measurement/test headings were separated.
Action
An action tracking table was created; responsible party, target date and closure status fields were added to the report.
Measurable output
4 open follow-up items, 2 closure notes and 1 next inspection date were recorded.
Follow-up result
Closed/open items were planned to be compared during the next visit.
Limit / note
These examples show the anonymized field experience format used by Pow-Sys.

Evidence Assets and Verification Points

The evidence, certificate and field output areas used on the Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair page are shown together with how users can verify them.

Evidence assetHow it appears on the pageTrust contribution
Authorization and certificate transparencyTechnical reviewer box, EMO/SMM information, certificates page and EMO verification linkMakes Expertise and Authority signals visible.
Anonymized field case recordsFacility types in Bursa and nearby areas, finding, action, measurable output and follow-up resultStrengthens Experience and original field-practice signals.
Anonymized masked report previewReport content, inspection heading, field check point, output, follow-up date fields and printable anonymized report preview documentHelps users understand the expected deliverable before requesting service.
Official source mappingTechnical claim, official basis and page section are shown in the same table.Improves Referenceability and Trust.
Update and correction trailLast updated date, change note, update history and correction policy linkShows that the content is current, auditable and responsibly maintained.

Proposal Scope: Included / Planned Separately

For Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair, included items and additional works that may be planned as separate services are stated clearly in the proposal.

ScopeStatusExplanation
Site survey and preliminary assessmentIncluded depending on proposalPlanned to clarify the service scope and site need.
Periodic site visit and written action reportIncludedFindings, risk level and follow-up notes are prepared according to the contract/service scope.
Grounding measurement, thermal imaging, relay testing or transformer oil analysisCan be planned separatelyQuoted as a separate test/measurement work when required.
Revision, implementation, material supply or maintenance-repairSeparate serviceImplementation needs arising from the report are evaluated under a separate scope.

Out-of-Scope and Separately Planned Works

Bursa Transformer Maintenance, Testing, Oil Analysis and Fault Repair produces technical follow-up, reporting, compliance assessment and risk notification. The following works are planned separately when required; final risk level, cost and scope are not confirmed without an on-site survey.

Out-of-scope / separate workWhy is it evaluated separately?Pow-Sys approach
Grounding measurementIt may require measurement equipment, site time and a separate report.The need is stated in the main report; measurement work is planned separately.
Relay testing and selectivityRelay settings, test equipment, outage planning and separate engineering assessment may be required.Quoted as a separate testing/selectivity service when needed.
Thermal imaging inspectionIt requires imaging under load and a separate thermal finding report.Planned separately for panels, switchgear or connections where risk is observed.
Transformer maintenance and oil analysisIt may require maintenance crew, sampling, laboratory work or a separate test procedure.The need is written in the technical report; maintenance/testing is prepared as a separate scope.
Project revision, implementation and physical remediationIt creates material, labor, authority process or implementation responsibility.The main service reports the finding; implementation and contracting works are handled separately.

Claim and Official Source Mapping

Technical and regulatory statements are evaluated together with the official sources listed on the page. This table makes the relation between each claim and its supporting basis visible.

SourceClaim supported on the pageWhere it is used
EMO certificate verification and SMM/YGTIS sourcesAuthorized engineer assessment, certificate transparency and authorization confirmation are required at service start.Technical reviewer, authorization, certificate verification and proposal preparation sections.
Applicable electrical installation regulationsFinal site decision is clarified through on-site review, current documents and authorized engineer assessment.Information note, out-of-scope works and field data methodology sections.
TS EN, IEC, TEDAS, TEIAS, utility or relevant authority processesTesting, measurement, maintenance, authority approval or implementation works may be planned separately.Decision matrix, proposal scope, official sources and report output sections.

Update History and Editorial Review

Pow-Sys service pages are periodically reviewed for regulatory, technical practice and field reporting topics. If inaccurate or outdated information is noticed, reports are received through the correction policy.

DateWhat changed?Where is it shown?
May 2026Service scope, report outputs, pre-proposal information and trust notes were reviewed for the current period.Shown in the 'Last updated', 'What changed?' and update history areas.
After a correction requestInaccurate, incomplete or outdated information is technically reviewed.Necessary corrections are updated as page text, source links or explanatory notes.
Transformer oil sampling, oil testing, oil analysis and grounding measurement in Bursa
Transformer maintenance and testing study where oil testing and DGA are reported together with grounding measurements.
Anonymous technical report, checklist and follow-up output example
Standard report/control output: field finding, risk level, corrective action and follow-up date shown together.

Official Regulatory Sources

Frequently Asked Questions

How often should transformer maintenance be performed? Is it mandatory?

For power and distribution transformers, the general approach is to perform comprehensive maintenance and routine tests at least once a year. In transformers with high loading, dusty-humid environments or critical processes, intermediate checks and oil testing / analysis can be repeated more frequently. Transformer maintenance is within periodic inspection obligations under Law No. 6331 and the Regulation on Health and Safety Conditions in the Use of Work Equipment.

Who can perform transformer maintenance?

Transformer maintenance should be performed by electrical / electrical-electronics engineers experienced in high voltage and trained technical teams who know the relevant standards and regulations and can work with suitable test devices. For MV transformers, working under the supervision of EMO-registered authorized engineers is important for both safety and official reporting.

Which transformer tests are performed?

The main electrical transformer tests we apply in the field are TTR (turns ratio), winding DC resistance, insulation (megger), power factor / tan-delta when required, short-circuit impedance, load and no-load loss measurements, vector group and magnetic balance checks, and partial discharge monitoring. Depending on the project, MV switchgear tests, protection relay tests, cable insulation tests, grounding resistance-touch voltage measurements and commissioning steps can also be included.

Why are transformer oil testing and DGA so important?

Transformer oil is a critical component that provides both insulation and cooling. Oil tests and DGA performed according to IEC/ASTM standards examine dielectric strength, moisture, acidity and gases formed in oil, revealing internal faults such as arcing, partial discharge, overheating and cellulose aging at an early stage. It should be repeated periodically especially in aged transformers, facilities with changing loading profiles or previous oil results approaching limits.

How can a faulty transformer be detected?

Fault indications include abnormal noise, smell or vibration, sudden changes in oil level, oil leakage, bushing cracks, abnormal temperature rise seen on thermal camera, frequent trips of protection relays and decreases in insulation / BDV values. When such signs are observed, the transformer should not be forced to remain energized; a specialist service capable of tests, oil analysis and visual checks should be called.

Can we receive on-site transformer repair service in Bursa?

Yes. We provide on-site fault maintenance-repair and mobile transformer repair service for organized industrial zones and industrial facilities in Bursa. Oil leaks, gasket and bushing problems, loose connections, hot spots, cooling system faults and protection relay setting problems can often be resolved on site with mobile equipment. For more comprehensive damage, workshop repair, oil treatment and additional testing are organized with partner workshops.

What is a transformer maintenance contract?

A transformer maintenance contract is a written agreement in which annual or multi-year maintenance, routine tests, oil tests and required MV switchgear-cable checks are planned in advance for the power and distribution transformers in your facility. Contracted maintenance prevents forgotten inspection dates, meets legal requirements regularly, reduces fault risks and makes budget planning more predictable.

Which acceptance tests and commissioning procedures are applied for a new transformer?

Before energizing a new or renewed transformer, visual and mechanical checks, insulation tests, TTR, winding resistance measurements, load / no-load loss tests, short-circuit impedance measurement, partial discharge checks and, where required, high-voltage withstand tests are performed. In parallel, MV switchgear tests, protection relay tests, grounding and touch voltage measurements are completed. These steps form the field acceptance and commissioning procedure.

Let us bring your project to life together.

Contact us now for a site survey and preliminary discussion.

Contact Us